MISSION USV 1.000 - 10.000 VA
Leistung |
|
Ausgang n | V |
Ausgang n | V |
Bauart |
- Beschreibung
- Technische Daten
- Downloads
- Schnellanfrage
Technische Daten MISSION USV 1.000 - 10.000 VA Leistung
MODEL |
MISSION 1000 |
MISSION 2000 |
MISSION 3000 |
|
RATED CAPACITY |
1000VA / 900W |
2000VA / 1800W |
3000VA / 2700W |
|
INPUT |
Input |
Single phase and earthing |
||
Voltage range |
115±5VAC-295±5VAC |
|||
Frequency range |
45Hz-55Hz@50HZ/55Hz-65Hz@60HZ |
|||
Power factor |
≥0.98 |
|||
ECO range |
Setting output voltage±20VAC |
|||
Bypass range |
186VAC-252VAC |
|||
THDi |
≤7%(100% non linear load) |
|||
Connection |
1x IEC |
1x Terminal L/N + T |
||
OUTPUT |
Output style |
Single phase and earthing |
||
Rated voltage |
208/220/230/240VAC |
|||
Power factor |
0.9 |
|||
Voltage precision |
±2% |
|||
Output Frequency |
Line mode |
1. When input frequency is in the range,the output frequency is the same as that of input. When input frequency is out of the range,the output frequency is (50/60±0.2)Hz when turn to battery mode |
||
Battery mode |
(50/60±0.2)Hz |
|||
Crest ratio |
3:1 |
|||
Transfer time |
Mains ←→ Battery = 0ms |
|||
Overload capacity |
Battery mode |
108%±5%<load≤150%±5% >30s cut off output and warn, 150%±5%<load<200%±5% > 300ms cut off output and warn |
||
Line mode |
108%±5%<load≤150%±5% > 30s transfer to bypass and warn 150%±5%<load<200%±5% >300ms transfer to bypass and warn |
|||
Efficiency |
Line mode |
Full load ≥88% |
||
Battery mode |
Full load ≥85% |
|||
ECO |
Full load ≥94% |
|||
Output voltage distortion |
≤3% (100% linear load) |
|||
≤5% (100% non linear load) |
||||
Connection |
2x IEC 1x Schuko |
6x IEC 1x Schuko - 1x Terminal L/N + T |
||
BATTERY |
Input battery voltage |
24VDC |
48VDC |
72VDC |
Internal battery capacity |
2 |
4 |
6 |
|
Internal battery type |
12V/7AH sealed lead acid maintenance free battery (only refers to standard UPS) |
|||
Backup time |
10min (only refers to standard UPS), as for long backup UPS, the backup time is determined by the capacity of battery. |
|||
Charge current (A) |
1 |
MODEL |
MISSION 6KVA |
MISSION 10KVA |
|
Capacity |
6KVA / 5.4KW |
10KVA / 9KW |
|
AC INPUT |
Input |
Single phase & Ground |
|
Power factor |
≥ 0.8 (input THDV ≤1%) |
||
Rated voltage |
220VAC / 230VAC / 240VAC |
||
Rated frequency |
50Hz/60Hz Automatically selected |
||
Voltage range |
120~276Vac |
||
Frequency range |
45~65Hz |
||
Bypass voltage range |
220Vac max:default +25% (+10% ,+15%,20% , 25%) 230Vac max:default +20% (+10% ,+15%,20% ) 240Vac max:default +15% (+10% ,+15%) |
||
min:default-45%(-20%, -30% , -45%, ) |
|||
Bypass frequency range |
±1%、±2%、±4%、±5%、±10% |
||
THDI |
≤3% (100% liner load,input THDV ≤1%) |
||
≤5% (100% non liner load,input THDV ≤1%) |
|||
Connection |
Terminal block |
||
BATTERY |
Battery number |
16 standard - 18/20 optional |
|
Battery type |
12V/7Ah |
12V/9Ah |
|
sealed lead acid maintenance free battery |
|||
Charge model |
Boost charge or float charge auto switch |
||
Charge time |
Boost charge up to 20Hr (Max) |
||
Charge current (Max) |
1A (Standard) |
||
AC OUTPUT |
Output type |
Single phase & Ground |
|
Voltage regulation |
±1.0% |
||
Voltage distortion(THD) |
less than 2% at 100% liner load |
||
less than 5% at 100% non-liner load |
|||
Rated voltage |
220V/230V/ 240Vac can be setted |
||
Power factor |
0.9 |
||
Frequency regulation |
±0.1% (stand alone) |
||
±0.25% (parallel operation) |
|||
Frequency |
Utility mode:tracking mains frequency |
||
Battery mode:50Hz/60Hz |
|||
Frequency track speed |
1Hz/s (stand alone) |
||
0.5Hz/s (parallel operation) |
|||
Load capacity (Mains, drop a level in battery mode) |
105 %~ 110 %,lasts 1 hour |
||
110%~125%,lasts 10 minutes |
|||
125%~150%, lasts 1 minute |
|||
>150%,switch to bypass immediately |
|||
Overload for bypass |
>95%, can not inverter-fed |
||
Load for a long time when rated output current under 125% |
|||
Bypass load capacity is controlled by bypass circuit breaker, tripping when circuit breaker operating current. |
|||
Crest factor |
3:1 |
||
Efficiency |
Line Mode |
Full Load ≥90% |
|
Battery Mode |
Full Load ≥88% |
||
ECO |
Full Load ≥96% |
||
Dynamic respond |
± 5.0% (100% balance load) |
||
≤5% in a cycle |
|||
Inverter output current limit |
When current instantaneous value is 2 ~ 3 times of rated current peaks (1.414 * rated power/(3 * 220)), the inverter will be conducted in each pulse current limit protection. |
Downloads und Tools zu MISSION USV 1.000 - 10.000 VA Leistung
Hier finden Sie alle Ressourcen (Datenblättern, Betriebsanleitungen, Software und Tools) um das Beste aus unseren Produkten herauszuholen.Anfrage zu MISSION USV 1.000 - 10.000 VA Leistung stellen
Füllen Sie das folgende Formular aus, um weitere Informationen zu diesem Produkt und individuellen Angeboten zu erhalten. Unser Team steht bereit, um Sie zu unterstützen. Sie erhalten während unserer Geschäftszeiten innerhalb von max. 2 Stunden eine Rückmeldung von uns oder Sie nutzen unseren Live-Chat links unten.WEITERE PRODUKTE ENTDECKEN
Leider konnten wir noch nicht alle Produkte aus unserem umfangreichen Sortiment in unsere Internetseite einpflegen. Rufen Sie einfach unter +49 7183 35600 an oder schreiben Sie an info@thiele-kg.de
In unserem vorhergehenden Online-Produktkatalog finden Sie noch mehr Artikel.